v2Effective August 24, 2026

This is a frozen, versioned document. Contracts cite this exact version and it will not change. Newer requirements are published at a new version URL; this one remains available indefinitely.

Supersedes v1

These requirements define the criteria a colocation facility must meet to host SF Compute capacity.

Every requirement is tagged with a Tier:

  • Core: a hard requirement the facility must meet
  • Nice-to-have: a miss may be accepted as a tradeoff against a remediation commitment
  • Reference: informational; collected during diligence

A facility that does not meet every Core requirement may still be engaged under a contract as long as there is a commitment to reach the requirements within a defined diligence window (e.g. a 60-day term sheet).

RequirementDetailTier
Total contiguous power≥2 MW contiguous (ramped delivery may be acceptable)Core
ProvisioningConfirmed at 100% loadCore
Generator≥ N+1 redundancy; on-site fuel under a continuous-replenishment contract; ≤ 30 s start; tested weekly–monthly; annual load test; fuel-resupply contract with < 24 h responseCore
UPS≥9 min runtime; batteries in a separate fire-rated roomCore
Utility feedsRedundant, diverse feedsNice-to-have
rPDUsRedundant power to each rackCore
Primary voltage208V for air-cooled, 415V or 480V for high-density/DLC buildsCore
Provider PDUs / racksOptional; SF Compute can provide its own. Provider-supplied PDUs must be switchedCore (if provider-supplied)

Build typeCoolingPer-rack densityTier
B300 NVL8Air30 kWCore
B300 NVL8DLC120 kWCore
GB300 NVL72DLC140 kWCore
R200 NVL8DLC192 kWCore
VR200 NVL72DLC230 kWCore

A DLC build that rejects part of its heat to air must also meet the air requirements for that portion.

RequirementDetailTier
CapacityTotal heat rejection confirmed at maximum thermal output across the build's mix of air and liquidCore
RedundancyN+1 or betterCore
Air filtrationMERV 9 or betterCore
Environmental setpoints68–71 °F, 40–72% RHCore
Cooling typeDry coolerNice-to-have
PUE~1.3 targetNice-to-have

RequirementDetailTier
ContainmentHot/cold separation, blanking panels and air bafflesCore
Airflow clearanceConfirmed at maximum thermal outputCore

RequirementDetailTier
CDUsCommissioned at ≥ N+1 with leak detection at connection pointsCore
Coolant programDocumented coolant treatment program (e.g. PG25 water/glycol); flush-and-fill stations with documented coolant-handling protocols. Verified during site diligenceCore

RequirementDetailTier
Access controlMeasures preventing unauthorized entry into the DC hall and access to hardwareCore
InspectionPhysical or virtual inspection of the facility on requestCore
Badge readersAt access pointsCore
Mantrap / vestibuleSecure entry at the entranceCore
Visitor logsAccess logs and trackingCore
Staffing & access24/7 staffing (on-site or NOC) and 24/7 access for SF ComputeCore
Fire detectionVESDACore
Perimeter fenceSite perimeter fencingNice-to-have

RequirementDetailTier
DIA / ISP connectionsAt least 2, with route diversityCore
Bandwidth2× 100 Gbps to the space, with route diversity (burstable acceptable)Core
Latency< 50 ms ping to AWS S3 or Cloudflare R2Core
Ingress / egressNo restrictions or meteringCore
CarriersCogent plus at least one additional tier-1 carrierCore
Cloud connectivity / peeringCloud on-ramps / peering available (AWS, GCP, Azure, Cloudflare)Nice-to-have
Meet-me roomsRedundant MMRs and multiple physical entrance routesNice-to-have

RequirementDetailTier
Facility tierMinimum Tier III; ≥ N+1Core
Power / cooling redundancy≥ N+1 on generator, UPS, and coolingCore
2N redundancy2N where availableNice-to-have

CertificationTier
SOC 2 Type IICore
PCI-DSSCore
ISO 27001Core
TIA-942 (Rated-3 or better)Nice-to-have
EN 50600 (Class 3 or better)Nice-to-have

RequirementDetailTier
CleanlinessClean space, free of dust and debris, with cable runs neatly bundledCore
Contiguous spaceSufficient for the deploymentCore
FloorRaised floor or slab that exceeds rack weight limitsCore
Loading & stagingLoading-dock access to the DC floor (ramp or lift to raised-floor height); secure staging / burn-in area.Core
Single-tenant cageDedicated cageNice-to-have
ConveyancePower from floor or overhead; overhead conveyance for fiberNice-to-have
Modular buildAcceptable for sites lacking infrastructure, subject to reviewNice-to-have
Floor loadingFloor bearing ≥ 3,000 lbs per rack (GB300); ≥ 4,000 lbs per rack (VR200)Core (NVL72 builds)
Ceiling heightReviewed during site diligence

Reference only: informational inputs, not enforced as pass/fail.

ItemDetailTier
LocationContinental US & CanadaReference
Lease term3-5 yearsReference
Clean / renewable powerPreferred; describe availability in your proposalReference